This parameter specifies the delay of the inverter’s
wake-up-from-sleep after running command is
given, the inverter will start to run and output after
the time set by P01.23 elapses to realize brake
release.
Setting range: 0.0–600.0s
When the inverter starts in direct start mode
(P01.00=0), set P01.30 to a non-zero value to
enter short-circuit brake.
During stop, if the running frequency of inverter is
below the starting frequency of brake after stop,
set P01.31 to a non-zero value to enter
short-circuit brake after stop, and then carry out
DC brake in the time set by P01.12 (refer to