HD2 Series Inverter Function Parameter List
-199-
continue running at the frequency defined by this
step in the remaining time.
0: second (s). The running time of each step is
counted in seconds.
1: minute (min). The running time of each step is
counted in minutes.
P11––Protection parameters
0x000–0x111
Ones:
0: Disable software input phase loss protection
1: Enable software input phase loss protection
Tens:
0: Disable output phase loss protection
1: Enable output phase loss protection
Hundreds:
0: Disable hardware input phase loss protection
1: Enable hardware input phase loss protection
Frequency-drop
at transient
power down
Energy braking in
standby state
Overvoltage stall
protection
Overvoltage stall
threshold
Output
frequency
Time t
Time t
DC bus voltage V
Overvoltage stall
protection
voltage
120–150% (standard bus voltage) (380V)
120–150% (standard bus voltage) (220V)
During accelerated running, as the load is too