HD2 Series Inverter Function Parameter List
-200-
Function
code
Name
Description
Default
value
Modify
selection
large, the actual acceleration rate of motor is lower
than that of output frequency, if no measures are
taken, the inverter may trip due to overcurrent
during acceleration.
0x00–0x11
Ones: Current-limit action selection
0: Invalid
1: Always valid
Tens: Hardware current-limit overload alarm
selection
0: Valid
1: Invalid
P11.06
Automatic
current-limit level
Current-limit protection function detects output
current during running and compares it with the
current-limit level defined by P11.06, if it exceeds
the current-limit level, the inverter will run at stable
frequency during accelerated running, or run in
decreased frequency during constant-speed
running; if it exceeds the current-limit level
continuously, the inverter output frequency will
drop continuously until reaching lower limit
frequency. When the output current is detected to
be lower than the current-limit level again, it will
continue accelerated running.
Output current A
Output frequency f
Current-limit
threshold
Set
frequency
Acceleration
Constant
speed
Time t
Time t
Setting range of P11.06: 50.0–200.0% (of the
rated inverter output current)
Setting range of P11.07: 0.00–50.00Hz/s
G type:
160.0%
P type:
120.0%
P11.07
Frequency-drop
rate during
current limit
10.00
Hz/s
P11.08
Inverter or motor
overload/underlo
ad pre-alarm
0x000–0x1132
Ones place:
0: Motor overload/underload pre-alarm, relative to
0x000