HD2 Series Inverter Function Parameter List
-201-
Function
code
Name
Description
Default
value
Modify
rated motor current
1: inverter overload/underload pre-alarm, relative
to rated inverter output current
2: inverter output torque overload/underload
pre-alarm, relative to rated motor torque
Tens place:
0: The inverter continues running after
overload/underload alarm.
1: The inverter continues running after underload
alarm and stops running after overload fault.
2: The inverter continues running after overload
alarm and stops running after underload fault.
3: The inverter stops running after
overload/underload fault.
Hundreds place:
0: Always detect
1: Detect during constant-speed running
Thousands place: inverter overload current
reference selection
0: Related to current calibration coefficient
1: Irrelated to current calibration coefficient
P11.09
Overload
pre-alarm
detection level
If the inverter or motor output current is larger than
the overload pre-alarm detection level (P11.09),
and the duration exceeds the overload pre-alarm
detection time (P11.10), overload pre-alarm signal
will be outputted.
Y,
RO1, RO2
Output current
Overload pre-alarm
threshold
Time t
Time t
Pre-alarm time tPre-alarm time t
Setting range of P11.09: P11.11–200% (relative
value determined by the ones place of P11.08)
G type:
150%
P type:
120%
P11.10
Overload
pre-alarm
detection time
1.0s