HD2 Series Inverter Function Parameter List
-202-
Setting range of P11.10: 0.1–3600.0s
Underload
pre-alarm
detection level
Underload pre-alarm signal will be outputted if the
output current of the inverter or motor is lower than
underload pre-alarm detection level (P11.11), and
the duration exceeds underload pre-alarm
detection time (P11.12).
Setting range of P11.11: 0–P11.09 (relative value
determined by the ones place of P11.08)
Setting range of P11.12: 0.1–3600.0s
Underload
pre-alarm
detection time
Fault output
terminal action
during fault
Used to set the action of fault output terminals
during undervoltage and fault reset.
0x00–0x11
Ones:
0: Act during undervoltage fault
1: Do not act during undervoltage fault
Tens:
0: Act during fault reset
1: Do not act during fault reset
Speed deviation
detection value
0.0–50.0%
This parameter is used to set the speed deviation
detection value.
Speed deviation
detection time
Used to set the speed deviation detection time.
Note: Speed deviation protection is invalid
when P11.15 is set to 0.0.
Speed
Actual detection
value
Set detection
value
Time t
t1
t2
t2=P11.15
t1<t2, so the VFD continues running
dEu
Running Fault output
Automatic
frequency-reducti
on during voltage
drop
Proportional
coefficient of
This parameter is used to set the proportional
coefficient of the bus voltage regulator during