HD2 Series Inverter Function Parameter List
-208-
Function
code
Name
Description
Default
value
Modify
motor 2
P12.15
Rated power of
synchronous
motor 2
0.1–3000.0kW
Depends
on model
P12.16
Rated frequency
of synchronous
motor 2
0.01Hz–P00.03 (Max. output frequency)
50.00Hz
P12.17
Number of pole
pairs of
synchronous
motor 2
1–128
2
P12.18
Rated voltage of
synchronous
motor 2
0–1200V
Depends
on model
P12.19
Rated voltage of
synchronous
motor 2
0.8–6000.0A
Depends
on model
P12.20
Stator resistance
of synchronous
motor 2
0.001–65.53
Depends
on model
P12.21
Direct-axis
inductance of
synchronous
motor 2
0.01–655.35mH
Depends
on model
P12.22
Quadrature-axis
inductance of
synchronous
motor 2
0.01–655.35mH
Depends
on model
P12.23
Counter-emf
constant of
synchronous
motor 2
0–10000V
300
P12.24
Reserved
0–0xFFFF
0x0000
P12.25
Reserved
0%–50% (of the motor rated current)
10%
P12.26
Overload
protection of
motor 2
0: No protection
1: Common motor (with low-speed compensation)
2: Frequency-variable motor (without low-speed
compensation)
2

Table of Contents