HD2 Series Inverter Function Parameter List
-213-
value.
In general, this parameter is set to 0.0. When
continuous communication is required, you can set
the function code to monitor communication status.
Transmission
error processing
0: Alarm and coast to stop
1: Do not alarm and continue running
2: Do not alarm and stop as per the stop mode
(Under communication control mode only)
3: Do not alarm and stop as per the stop mode
(Under all control modes)
Modbus
communication
processing action
0x00–0x11
Ones:
0: Write operation has response
1: Write operation has no response
Tens:
0: Communication password protection is invalid
1: Communication password protection is valid
Hundreds place: Valid only for RS485
communication
0: User-defined addresses specified by P14.07
and P14.08 are invalid
1: User-defined addresses specified by P14.07
and P14.08 are valid
User-defined
running
command
address
0x0000–0xFFFF
P14.08
User-defined
frequency setting
address
0x0000–0xFFFF 0x2001
○
P14.09
Modbus TCP
communication
timeout time
0.0–60.0s 5.0
○
P14.10
Enabling
program upgrade
through RS485
0–1
0: Disable
1: Enable
0
◎
P14.11
Bootloader
software version
0.00–655.35 0.00
●
P14.12 Displaying no 0–1 0
○