HD2 Series Inverter Function Parameter List
-213-
Function
code
Name
Description
Default
value
Modify
value.
In general, this parameter is set to 0.0. When
continuous communication is required, you can set
the function code to monitor communication status.
P14.05
Transmission
error processing
0: Alarm and coast to stop
1: Do not alarm and continue running
2: Do not alarm and stop as per the stop mode
(Under communication control mode only)
3: Do not alarm and stop as per the stop mode
(Under all control modes)
0
P14.06
Modbus
communication
processing action
0x00–0x11
Ones:
0: Write operation has response
1: Write operation has no response
Tens:
0: Communication password protection is invalid
1: Communication password protection is valid
Hundreds place: Valid only for RS485
communication
0: User-defined addresses specified by P14.07
and P14.08 are invalid
1: User-defined addresses specified by P14.07
and P14.08 are valid
0x000
P14.07
User-defined
running
command
address
0x0000–0xFFFF
0x2000
P14.08
User-defined
frequency setting
address
0x0000–0xFFFF 0x2001
P14.09
Modbus TCP
communication
timeout time
0.0–60.0s 5.0
P14.10
Enabling
program upgrade
through RS485
0–1
0: Disable
1: Enable
0
P14.11
Bootloader
software version
0.00–655.35 0.00
P14.12 Displaying no 0–1 0