HD2 Series Inverter Function Parameter List
-254-
Function
code
Name
Description
Default
value
Modify
1: Filter
Bit5: Pulse reference filter mode
0: Self-adaptive filter
1: Use P24.19 filter parameters
Bit6: Frequency-divided output source setting
0: Encoder signals
1: Pulse reference signals
Bits7–15: Reserved
P24.18
Encoder pulse
filter width
0–63
The filtering time is P24.18×0.25 μs. The value 0
or 1 indicates 0.25 μs.
2
P24.19
Pulse reference
filter width
0–63
The filtering time is P24.19×0.25 μs. The value 0
or 1 indicates 0.25 μs.
2
P24.20
Pulse number of
pulse reference
0–16000
1024
P24.21
Enable angle
compensation of
synchronous
motor
0–1
0
P24.22
Switchover
frequency
threshold of
speed
measurement
mode
0–630.00Hz
1.00Hz
P24.23
Synchronous
motor angle
compensation
coefficient
-200.0–200.0%
100.0%
P24.24
Number of pole
pairs in inital
magnetic pole
angle autotuning
1–128
2
P25––Extension I/O card input functions