Chapter 6 Troubleshooting                                                                                            IS620P User Manual                                                 
- 142 -
Cause Conrming Method Corrective Action
6. Locked-rotor occurs 
due to mechanical 
factors, resulting 
in very heavy load 
during running.
 
•
Check the running reference and the 
actual motor speed (H0B-00) by using 
the drive debugging platform of Inovance 
or the operation panel. 
Running reference in the position control 
mode: H0B-13 (input reference pulse 
counter)
Running reference in the speed control 
mode: H0B-01 (speed reference)
Running reference in the torque control 
mode: H0B-02 (internal torque reference)
Check the running reference in 
corresponding mode is not 0 but the 
motor speed is 0.
Eliminate mechanical factors.
7. The servo drive is 
faulty.
 
•
The fault remains after the servo drive is 
powered off and then powered on again.
Replace the servo drive.
You can clear the fault or re-power on the system 30s after occurrence of the overload fault.
27. Er.630: Overheat protection of locked-rotor motor
Cause:
 
•
The actual motor speed is lower than 10 rpm but the torque reference reaches the limit. 
The duration reaches the value set in H0A-32.
Cause Conrming Method Corrective Action
1. The power output 
phase (UVW) loss 
or incorrect phase 
sequence occurs on 
the servo drive.
 
•
Perform motor trial running when the 
motor has no load and check the motor 
wiring.
Connect the motor cables 
correctly again or replace 
them.
2. The UVW cables 
or the encoder cable 
breaks.
 
•
Check the wiring.
Connect the motor cables and 
encoder cable correctly again 
or replace them.
3. The motor rotor 
is locked due to 
mechanical factors.
 
•
Check the running reference and the 
actual motor speed (H0b-00) by using the 
drive debugging platform of Inovance or 
the operation panel. 
Running reference in the position control 
mode: H0B-13 (input reference pulse 
counter)
Running reference in the speed control 
mode: H0B-01 (speed reference)
Running reference in the torque control 
mode: H0B-02 (internal torque reference)
Check whether the running reference 
in corresponding mode is not 0 but the 
motor speed is 0.
Eliminate mechanical factors.