IS620P User Manual                                                                      Chapter 4 Running and Commissioning
- 79 -
Function 
Code
Parameter Name Setting Range Unit Default
Effective 
Time
Property
Control 
Mode
H05 07
Electronic gear ratio 
1 (numerator)
1–1073741824 - 1048576 Immediate
During 
running
P
H05 09
Electronic gear 1 
(denominator)
1–1073741824 - 10000 Immediate
During 
running
P
H05 11
Gear ratio 2 
(numerator)
1–1073741824 - 1048576 Immediate
During 
running
P
H05 13
Gear ratio 2 
(denominator)
1–1073741824 - 10000 Immediate
During 
running
P
The following gure shows the working principle of the electronic gear ratio.
Figure 4-3 Working principle of the electronic gear ratio
Position 
loop
B
A
Position reference
(reference unit)
PMSM
PG
Speed 
loop
Current 
loop
Position feedback (pulses)
Position 
reference 
(pulses)
When H05-02 is 0 and the motor is connected to the load through the reduction gear, assume 
that the reduction ratio between the motor shaft and the load mechanical side is n/m (the load 
shaft rotates n revolutions when the motor shaft rotates m revolutions), and the formula of 
calculating the electronic gear ratio is as follows:
Electronic gear ratio
B
A
=
H05-07
H05-09
Encoder resolution
Displacement (command unit) when 
the load shaft rotates one revolution
m
n
x
=
The IS620P supports two electronic gear ratios, which can be switched over by using the 
function FunIN.24. 
When H05 ≠ 0:
Electronic gear ratio
B
A
=
Encoder resolution
H05-02
Function 
Code
Parameter Name Setting Range Unit Default
Effective 
Time
Property
Control 
Mode
H05 02
Pulses for one 
motor revolution
0–1048576 P/Rev 0
Power-on 
again
At stop P
When this parameter is set, the electronic gear ratio is irrelative to H05-07, H05-09, H05-11 
and H05-13, and the electronic gear ratio switchover is not supported.