D3-DU 3xx/A, /BTechnical data
Project engineering manual V1.09
116
© KEBA 2021
Short circuit-proof: Yes
Overload protection: No
Cross-wire monitoring: Yes
Isolation: No
Safety Category:
● Single output: Up to category 3, PL d, SIL 2
● Redundant output: Up to category 4
*)
, PL e, SIL3
Voltage at switched of output: Max. 2.4 V
Output testing:
Always active (Test pulse: max. 600 μs, mini-
mum range between two test pulse: 4 ms)
Effect by incorrectly connection (external
voltage on output):
Potential defect
*)
Category 4 hence PL e and therefore PL e are only valid, if the following
SDOs pairs are used: SDO0 + SDO1, SDO2 + SDO3, SDO4 + SDO5, ...
12.9 (Only for D3-DU 3x5/x) safe relais outputs (SRO)
Quantity: 2
Type: Normally Open, not self-retaining
Nominal voltage:
DC1: 24 V DC / DC13: 24 V DC / AC1: 230 V
AC
Nominal current: DC1: 4 A / DC13: 3.3 A / AC1: 4 A
Inrush current: Max. 30 A for 20 ms
Isolation voltage: 3000 V AC
Switch voltage range: 5 V to 250 V (AC and DC)
Switch power range: 40 mW to 1.500 W (VA)
Switch frequency mechanical: 15 Hz
Disengaging time (RK closed): Typical 3 ms (without wiring of the coil)
Capacitive Load: max. 200 nF
Cross-circuiting detection:
No (with pre-fuse SCPD 6 A gG/ gL to 1.000
A)
Overload protection: No
Isolation: Yes
Mechanical lifetime: Min. 10
7
switching cycles
Electrical lifetime: AC1 (360 S/h) > 90.000
Status display: Orange LED at front side
Safety Category:
● Single output: Up to category 2, PL c, SIL 2
*)
● Redundant output: Up to category 4, PL e, SIL 3
*)
Output testing: No
Effect by incorrectly connected outputs: Potential defect