17 Appendix: Response time
The following tables specifies the max. guaranteed response time, which is
necessary from activation of a safety input to deactivation of a safety output.
The specified response times are valid, if the connection (FSoE connection
to encoder box or PROFISafe connection to superior safety control) is oper-
ated with the specified watchdog and the safety application logic has no fur-
ther delays. Otherwise the response time is higher. For further information
contact KEBA. For error reaction times of slave module please contact the
corresponding manufacturers.
Safety control
Activation
Deactivation
digital output
Deactivation
safe relay output
Digital input on safety control 38 ms 61 ms
Digital input on encoder box 52 ms
1)
75 ms
1)
Digital input on EL1904 45 ms
1)
68 ms
1)
Digital input on EP1908 48 ms 71 ms
Digital input on EL1918 48 ms 71 ms
Digital input on BWU3418 200 ms
1)
--
Response on a violated single axis monitor-
ing block or robot monitoring block
48 ms
1)
71 ms
Control via FSoE Master (EL6900) 105 ms
3)
--
Control via PROFISafe Master 190 ms
3)
--
Virtual input (functional control) 43 ms 66 ms
Encoder box
Activation
Deactivation
digital output
Digital input on safety control 62 ms
1)
Digital input on encoder box 72 ms
1)
Digital input on EL1904 68 ms
2)
Digital input on EP1908 68 ms
Digital input on EL1918 68 ms
Response on a violated single axis monitoring block or robot moni-
toring block
70 ms
1)
In case of failure the reaction time of the safe digital outputs of the encoder
box is increased by 4 ms.
EL2904
Activation
Deactivation
digital output
Digital input on safety control 55 ms
2)
Digital input on encoder box 64 ms
2)