Table 1. Limits for particulates and gases
Contaminant Limits
Reactive gases
Severity level G1 as per ANSI/ISA 71.04-1985
1
:
• The copper reactivity level shall be less than 200 Angstroms per month (Å/month ≈ 0.0035 μg/
cm
2
-hour weight gain).
2
• The silver reactivity level shall be less than 200 Angstroms per month (Å/month ≈ 0.0035 μg/
cm
2
-hour weight gain).
3
• The reactive monitoring of gaseous corrosivity must be conducted approximately 5 cm (2 in.) in
front of the rack on the air inlet side at one-quarter and three-quarter frame height off the floor
or where the air velocity is much higher.
Airborne
particulates
Data centers must meet the cleanliness level of ISO 14644-1 class 8.
For data centers without airside economizer, the ISO 14644-1 class 8 cleanliness might be met by
choosing one of the following filtration methods:
• The room air might be continuously filtered with MERV 8 filters.
• Air entering a data center might be filtered with MERV 11 or preferably MERV 13 filters.
For data centers with airside economizers, the choice of filters to achieve ISO class 8 cleanliness
depends on the specific conditions present at that data center.
• The deliquescent relative humidity of the particulate contamination should be more than 60%
RH.
4
• Data centers must be free of zinc whiskers.
5
1
ANSI/ISA-71.04-1985. Environmental conditions for process measurement and control systems: Airborne
contaminants. Instrument Society of America, Research Triangle Park, North Carolina, U.S.A.
2
The derivation of the equivalence between the rate of copper corrosion growth in the thickness of the corrosion
product in Ã…/month and the rate of weight gain assumes that Cu2S and Cu2O grow in equal proportions.
3
The derivation of the equivalence between the rate of silver corrosion growth in the thickness of the corrosion
product in Ã…/month and the rate of weight gain assumes that Ag
2S is the only corrosion product.
4
The deliquescent relative humidity of particulate contamination is the relative humidity at which the dust absorbs
enough water to become wet and promote ionic conduction.
5
Surface debris is randomly collected from 10 areas of the data center on a 1.5 cm diameter disk of sticky
electrically conductive tape on a metal stub. If examination of the sticky tape in a scanning electron microscope
reveals no zinc whiskers, the data center is considered free of zinc whiskers.
Management options
The XClarity portfolio and other system management options described in this section are available to help
you manage the servers more conveniently and efficiently.
Chapter 1. Introduction 11

Table of Contents

Other manuals for Lenovo ThinkSystem SR665 V3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenovo ThinkSystem SR665 V3 and is the answer not in the manual?

Lenovo ThinkSystem SR665 V3 Specifications

General IconGeneral
Cores per ProcessorUp to 96 cores
Form Factor2U Rack
ManagementLenovo XClarity Controller
ProcessorAMD EPYC 9004 Series
MemoryUp to 6TB DDR5
Memory Slots32x DIMM slots
StorageUp to 40x 2.5" drives
Drive BaysUp to 40x 2.5" or 20x 3.5" drives (front and rear)
RAID SupportRAID 0, 1, 10, 5, 50, 6, 60
Expansion SlotsUp to 7 PCIe 5.0 slots
Network1GbE, 10GbE, 25GbE
Power SupplyUp to 2x hot-swap redundant power supplies
Operating System SupportWindows Server, VMware

Related product manuals