IMPULSE•VG+ Series 3 Instruction Manual – 07/25/05
5-6
Sequence/Reference Source
B3-01 and B3-02 determine the source from where the frequency reference and RUN command are
generated.
Parameter
Code Display Function Range
Initial
Value
Access
Level
B3-01 Reference Source Source from where the frequency
reference is generated.
0-4 1 Adv
0 Operator Digital operator (Keypad).
1 Terminals Control circuit terminal
2 Communication Serial communication (Port 6CN).
3 Option PCB Optional card (Port 2CN).
4 Pulse Input (H6-01) Pulse input.
B3-02 Run Source Source from where the RUN
command is generated.
0-3 1 Adv
0 Operator Digital operator (Keypad).
1 Terminals Control circuit terminal.
2 Communication Serial communication (Port 6CN).
3 Option PCB Optional card (Port 2CN).