IMPULSE•VG+ Series 3 Instruction Manual – 07/25/05
5-38
Slack Cable Detection
IMPULSE•VG+ Series 3 offers Slack Cable Detection in the hoist application. The Slack Cable
condition is detected when the torque output is drastically reduced and has dipped below a set-point
(C11-03) level. When Slack Cable condition occurs, the output action is defined by the C11-02
which has 6 selections.
The Slack Cable Detection is not executed, unless both of the following conditions are true:
The output frequency is between C11-04 and C11-06.
The Slack Cable Detection delay time is between C11-05 and C11-07.
Setup Procedure:
To set the Slack Cable Detection torque level (C11-03), by lowering the hoist without
load at a constant speed that the hoist would normally run during the operation.
Monitor and record the torque reference (U1-09). Repeat above operation several
times to ensure an accurate reading.
Then Set C11-03 = [(U1-09)-2].
Enable Slack Cable Detection by setting the C11-01 to 1.
Select output action when Slack Cable is detected by defining C11-02.
Parameter
Code Display Function Range Initial Value
Access
Level
C11-01 Slack Cable 0/1 (For Hoist Application)
Determines whether Slack
Cable Detection is enabled.
0~1 0 Adv
0 Disabled
1 Enabled
C11-02 Action at SLC Multi-function output that
occurs at Slack Cable
Detection. For all Selections,
RAISE command is permitted
(MFO=28).
0~5 2 Adv
0 No Action Alarm Only
1 No Act/C3-04 Next LOWER command is at
Lower Limit 1 speed (C3-04).
2 Decel/C3-04 Decelerate to Lower Limit 1
Speed C3-04. Continued
LOWER commands allowed,
but at C3-04.
3 Decel/No Opr Decelerate to Lower Limit 1
Speed C3-04. Continued
LOWER commands are not
allowed.
4 Dec Stop/C3-04 Decel (by C3-05) to Lower
Limit 1 Speed C3-04.
Continued LOWER
commands allowed, but at C3-
04.
5 Dec Stop/No Opr Decel (by C3-06) to stop.
Continued LOWER
commands are not allowed.

Table of Contents

Other manuals for Magnetek IMPULSE VG+ Series 3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Magnetek IMPULSE VG+ Series 3 and is the answer not in the manual?

Magnetek IMPULSE VG+ Series 3 Specifications

General IconGeneral
BrandMagnetek
ModelIMPULSE VG+ Series 3
CategoryController
LanguageEnglish

Related product manuals