Initial Parameters (A1-05)
Use this parameter to reset the inverter to its factory default settings.
Password Entry (A1-06)
This parameter will enable the user to set a password that will inhibit the programming of the A1-01
to A1-03 parameters. This function is useful when used in conjunction with the access level
parameter A1-01. To set the password, press the MENU and RESET buttons at the same time and the
display will change from A1-06 to A1-07. Program in a password number, then when A1-06 is not
the same as A1-07 parameter A1-01 to A1-03 cannot be changed. When A1-06 is the same as A1-07,
then A1-01 to A1-03 can be changed.
User Parameters (A2-01 through 32)
The user can select up to 32 parameters for quick-access programming. By setting the user access
level (A1-01) to “User Program,” only the parameters selected in function A2 can be accessed by the
user. To assign a parameter as a user parameter go to the A2 level in the initialize menu. Once the A2
parameters are set and A1-01 is programmed to “User Program,” only the parameters visible in the
program menu will be assigned to an A2 parameter.
Setting Description
0 No Initialization (factory default)
1110 User Initialization - resets the inverter to user-specified initial values. To set
user-specified initial values, make all required changes to parameter settings,
then set 02-03 to “1”. The inverter will memorize all current settings as the
user-specified initial values. Up to 50 changed parameters can be stored.