Jump Frequencies
This function allows the “jumping” of critical frequencies so that the motor can operate without
resonant vibrations caused by some machine systems. This function is also used for deadband
control. Setting the value to 0.0 Hz disables this function.
Figure 5-8: Jump Frequencies
Parameter
Code Display Function Range Initial Value
Access
Level
B8-01 Jump Freq 1 First of three jump
frequencies.
0.0–150.0 Hz 0.0 Adv
B8-02 Jump Freq 2 Second of three jump
frequencies.
0.0–150.0 Hz 0.0 Adv
B8-03 Jump Freq 3 Third of three jump
frequencies.
0.0–150.0 Hz 0.0 Adv
B8-04 Jump Bandwidth Jump frequency reference
bandwidth.
0.0–20.0 Hz 1.0 Adv
HZ
H
Z
F
requency
Output
Set Frequency Range
B8-01
B8-02
B8-03
B8-04
B8-04
B8-04