IMPULSE•VG+ Series 3 Instruction Manual – 07/25/05
5-41
Maintenance Timer
The “Maintenance Timer” is a maintenance feature that will alert an operator, for example, when the
bearings need to be greased. It consists of a Multi-Function output (Data 37) that becomes active
when the total running time has exceeded the amount of time (in hours) programmed in parameter
C12-05 and the frequency reference will be multiplied by a programmable gain (C12-06) to slow the
motion down until the bearings have been greased. An alarm will also be posted on the Keypad
stating “Maintenance Required”. Once the bearings have been greased, the output and alarm
message can be reset by two different methods. One method is through a Multi-Function Input
programmed for Maintenance Reset (H1-01 ~ 06 = 5A) and the second method is by pressing the
Mode/Service (Local/Remote) button three consecutive times with no more than 2 seconds between
presses. Press enter to reset timer. A message will then appear on the keypad stating that the timer
has been reset. The Multi-Function Output will turn off at this time. When C12-0 = 0, the function is
disabled.
Parameter
Code Display Function Range Initial Value
Access
Level
C12-05 Maintenance Tmr Maintenance Timer Trip
Level
0-32767 0 Adv
C12-06 Maintenance Gain Speed Reference Gain 0.00-1.00 0.5 Adv

Table of Contents

Other manuals for Magnetek IMPULSE VG+ Series 3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Magnetek IMPULSE VG+ Series 3 and is the answer not in the manual?

Magnetek IMPULSE VG+ Series 3 Specifications

General IconGeneral
BrandMagnetek
ModelIMPULSE VG+ Series 3
CategoryController
LanguageEnglish

Related product manuals