IMPULSE•VG+ Series 3 Instruction Manual – 07/25/05
5-63
Communication Option Cards
Settings for DP-RAM option cards.
Parameter
Code Display Function Range
Initial
Value
Access
Level
F6-01 Com Bus Flt Sel Stopping method at communication
error.
0-4 1 Adv
0 Decel to Stop
1 Coast to Stop
2 Fast Stop
3 Use B3-03 Method
4 Alarm only
F6-02 EFO Detection Option External Fault 0-1 0 Adv
0 Always Detected
1 Only During Run
F6-03 EFO Fault Action Option External Fault 0-4 1 Adv
0 Decel to Stop
1 Coast to Stop
2 Fast Stop
3Use B3-03
4Alarm Only
F6-05 Current Unit Sel Current Unit 0-1 0 Adv
0A Display
1 100%/8192
F6-06 Torq Ref/Lmt Sel Torque Reference Limit Selection 0-1 0 Adv
0 Disabled
1 Enabled