EasyManuals Logo

M&M RWB series User Manual

Default Icon
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #150 background imageLoading...
Page #150 background image
Standard Screw Compressor - RWB Series
C-10
M&M
R
EFRIGERATION
I
NC
.
NOTE: 0x80 has been added to the function code.
The following error codes are supported:
Unit Address 0x??
Function Code 0x90
Error Code 0x03
CRC 0x??
HEX
CODE
ERROR CODE DEFINITION
01 Illegal Function. The function code in the message is not supported.
02 Illegal Data Address. The data address in the message is invalid.
03
Illegal Data Value. At least one data element in a Preset Multiple Registers command was
invalid.
07
Negative Acknowledge. The command or data sequence is currently not allowed. This
response is usually caused by the failure of the master to set the Network In Control register
prior to writing other commands or setpoints. It may also be caused by commands not cur-
rently allowed by the mode or state of the compressor.