Standard Screw Compressor - RWB Series
3-36
M&M
R
EFRIGERATION
I
NC
.
High Suction Pressure Setpoints
The High Suction Pressure alarm and failure setpoints are not scheduled and are
active regardless of which group is in control.
High Suction Pressure Setpoints Screen
The following table lists the data entry fields for the High Suction Pressure Set-
points screen.
High Suction Pressure Data Definitions
M & M REFRIGERATION 8:32
AM
1. START
HIGH SUCT SETPTS
2. STATS
3. MODE
HIGH FAILURE XXX.X
PSIG
4. SETPT
HIGH ALARM XXX.X
PSIG
5. SCHED
6. CNTRL
7. MISC
8. LOGS
9. MENUS
TERM DEFINITION RANGE
HIGH
FAILURE
The compressor is failed (stopped) when this value is
exceeded.
29.9
INHG
-
185
PSIG
HIGH
ALARM
The CCS reports an alarm to the operator when this value is
exceeded.
29.9
INHG
-
185
PSIG