105
CHAPTER 4 FUNCTIONS
4
4.2 Transient Transmission Function
4.2.5 Changing the number of transient transmissions
4.2.5 Changing the number of transient transmissions
The number of transient transmissions that one station can execute during one link scan can be changed. ( Page
201, Section 6.3.6)
When a large number is set, if multiple transient requests are made in one link scan, the link scan time will be increased
temporarily. Therefore, do not set a number larger than necessary.
When the fixed link scan time is desired, use the feature of the cyclic transmission punctuality assurance. ( Page
80, Section 4.1.6)