124
4.4 RAS Functions
This section explains the RAS functions.
4.4.1 Control station switching function
Even if the control station goes down, a normal station (sub-control station) takes over the control to continue data link.
While the control station status is switched, data link stops for a period of a data link monitoring time (up to two seconds).
( Page 183, Section 6.3)
Data immediately before the stop are held during data link stop.
While data link is stopped, the own station identifies all other stations as faulty.
Even if cyclic transmission of the control station is stopped with a programming tool, the control station status is not
switched. ( Page 91, Section 4.1.12)
The control station status can be switched to a normal station where cyclic transmission has stopped with a programming
tool. ( Page 91, Section 4.1.12)
Switching
Control station
No.1
Sub-control station
No.2
Normal station
No.4
Normal station
No.3
Down