EasyManua.ls Logo

Mitsubishi Electric MELSEC-Q Series - Appendix 4.4 Precautions for System Replacement

Mitsubishi Electric MELSEC-Q Series
674 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
636
Appendix 4.4 Precautions for system replacement
The following describes the precautions for replacing the MELSECNET/H with the CC-Link IE Controller Network.
(1) Optical fiber cable
(a) Applicable optical fiber cable
The cable for the MELSECNET/H module cannot be used in the CC-Link IE Controller Network module.
Optical fiber cable that can be used in the CC-Link IE Controller Network: Page 38, Section 2.2.1
(b) Station-to-station distance
The station-to-station distance for the CC-Link IE Controller Network is up to 550m.
When the station-to-station distance is longer than 550m, shorten it to 550m or less.
(2) Content set by switch of the MELSECNET/H module main body
Setting should be made at network parameters in the CC-Link IE Controller Network module.
(3) Diversion of network parameters
When changing "Network Type" with a programming tool, data set is canceled.
When diverting network parameters, copy the setting contents to text editor etc. before changing "Network Type".
Copy can be made from [Copy] under [Edit] in the programming tool.
Remark
The operations of cutting, copying, or pasting network parameters cannot be performed in some range.
( GX Developer Version Operating Manual)
( GX Works2 Version Operating Manual (Common))