CHAPTER 7 PROCESSING TIME
7
7.2 Link Refresh Time
7.2.1 Interlink transmission time
7.2.1 Interlink transmission time
The following are the calculation formulas for the interlink transmission time.
(1) For High Performance model QCPUs, Process CPUs, and Redundant CPUs
*1 Total number of link device points for the range set by refresh parameters and set in the network range assignment. Note
that the points assigned to reserved stations are excluded.
*1 Indicates base units on which the CC-Link IE Controller Network module is mounted.
L: Interlink transmission time
LB: Total number of actual link refresh points in LB
*1
LW: Total number of actual link refresh points in LW
*1
KM4 and KM5: Constant
CPU type
KM4(×10
-3
) KM510
-3
)
Main base
*1
Extension
base
*1
Main base
*1
Extension
base
*1
High
Performance
model QCPU
Q02CPU 600 610 140 280
Q02H/Q06H/Q12H/Q25HCPU 250 270 130 260
Process CPU Q02PH/Q06PH/Q12PH/Q25PHCPU 250 270 130 260
Redundant
CPU
Q12PRH/Q25PRHCPU 250 130
αL=KM4+KM5× [ms]