10.1.7 Transient transmission is disabled
The following flowchart shows the procedures to be taken when transient transmission is disabled.
Is D LINK LED of own or
another station ON or flashing?
ON/flashing
"0"
What is control data completion status?
OFF
"Other
than 0"
Incorrect
Failed
Completed normally
Correct
Test result?
Are Target station's CPU type,
Target network No. and Target station No.
in control data correct?
Execute a communication test using the programming tool.
Check the sequence program of other stations
(for overwriting of data).
Check the error details by the error code and take
corrective actions.
Modify the control data.
Modify routing parameters.
End
Relevant bit ON
(Baton pass
error station)
Relevant bit OFF
(Normal baton pass station)
Baton pass status of each station
(SW00A0 to SW00A7)
Connect the programming tool to another station.
Check error factors in the CC IE Control
diagnostics, and take corrective actions according
to the troubleshooting section.
ON
(Station No.
not set)
OFF (Station No. set)
Station No. setting status
(own station) (SB0070)
Using the UINI instruction, set station No.
Transient transmission is disabled.
Page 476, Section 9.18
Page 511, Section 10.2
Page 324, CHAPTER 9
Page 238, Section 6.9
Page 174, Section 5.7.1
Page 500, Section 10.1.4
Page 541, Section 10.4