7.5 Cyclic Data Retention Time for System Switching in a
Redundant System
This section gives calculation formulas for cyclic data retention time that is taken when a system switching occurs in a
redundant system.
(1) When the control system power supply module is faulty or powered off or
when the control system CPU is faulty or reset
(a) When a redundant system is the control station and "System switching time of
Redundant CPU (Tsw) < Control station switching time (Csw)" is met
*1 For details, refer to the following.
QnPRHCPU User's Manual (Redundant System)
Th = Csw+ SS [ms]
Th: Cyclic data retention time
Tsw: System switching time of Redundant CPU
*1
Csw: Control station switching time = 20 + Constant link scan set value ( Page 201, Section 6.3.6 (1))
SS: Sequence scan time of Redundant CPU
*1