10.1.6 Cyclic transmission is disabled
No
Cyclic transmission is disabled.
Yes
Yes
OFF/
flashing
Is D LINK LED of own or
another station turned ON?
ON
No
Is the same shared group
as for the own station set when
the group cyclic transmission
function is used?
Does the station have a
CPU other than Basic model
QCPU or safety CPU?
In "Network range assignment" of the control station,
check the shared group.
Stations of Basic model QCPUs or safety CPUs
cannot receive other stations' data set in the area
of LB/LW 4000 or higher.
Assign the data required for them within the range
of LB/LW 0 to 3FFF.
1)
D LINK LED is OFF
D LINK LED is flashing