EasyManua.ls Logo

Mitsubishi Electric MELSEC-Q Series - Error Code List

Mitsubishi Electric MELSEC-Q Series
674 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
514
10.2.2 Error code list
Error code Error Error detail Corrective action
4000
H
to
4FFF
H
Errors detected by the CPU module
( Troubleshooting in the QCPU User's Manual (Hardware Design, Maintenance and Inspection))
7000
H
to
7FFF
H
Errors detected by the serial communication module, etc.
( Troubleshooting in the Serial Communication Module User's Manual)
B000
H
to
BFFF
H
Errors detected by the CC-Link system
( Troubleshooting in the CC-Link System Master/Local Module User's Manual)
C000
H
to
CFFF
H
Errors detected by the Ethernet interface module
( Troubleshooting in the Ethernet Interface Module User's Manual)
D000
H
to
DFFF
H
Errors detected by the CC-Link IE Field Network
( Troubleshooting in the CC-Link IE Field Network User's Manual)
E000
H
to
E005
H
Network module error The hardware has failed. • Please consult your local Mitsubishi representative.
E006
H
Receive queue full The receive queue is full.
• Temporarily stop the transient transmission, and then
retry it.
• Reduce the operation frequency of transient
transmission, and then retry the operation.
• Using the COM instruction, increase the processing
frequency of transient transmission.
( Page 326, Section 9.2.1)
• If the error persists even after taking the above actions,
please consult your local Mitsubishi representative.
E007
H
to
E011
H
Network module error The hardware has failed. • Please consult your local Mitsubishi representative.
E012
H
Parameter check result error
The network parameter
setting is not correct.
• Write correct network parameters to the programmable
controller.
• If the error persists even after taking the above action,
please consult your local Mitsubishi representative.
E013
H
E014
H
to
E018
H
Network module error The hardware has failed.
• Please consult your local Mitsubishi representative.
E019
H
CPU module error
No response has been
received from the CPU for 5
seconds.
E01A
H
CPU module stop error
A stop error has occurred in
the CPU module.
• Check the error in "PLC Diagnostics" of the
programming tool, and take corrective actions.
E01B
H
CPU module power failure
Power failure occurred in the
CPU module.
• The CPU module has been powered off.
Power it on again.
E01C
H
Network module error The hardware has failed. • Please consult your local Mitsubishi representative.

Table of Contents

Other manuals for Mitsubishi Electric MELSEC-Q Series

Related product manuals