515
CHAPTER 10 TROUBLESHOOTING
10
10.2 Error Codes
10.2.2 Error code list
E01D
H
IP packet transfer function not
supported (IP communication
test)
The CPU module which has
detected an error does not
support the IP packet transfer
function.
• Check the serial number (first five digits) of the CPU
module to check whether the module supports the
function.
If the module does not support the function, replace it
with the CPU module of the latest version.
E101
H
Parameter error
Some of the network
parameters is incorrect.
• Write correct network parameters to the programmable
controller.
• If the error persists even after taking the above action,
please consult your local Mitsubishi representative.
E102
H
Reserved own station error
The own station was set as a
reserved station.
• Cancel the reserved station setting in "Network Range
Assignment" of the control station.
• Change the station No. to the one that is not specified
as a reserved station.
E103
H
Invalid own station No.
The own station No. set is
outside the range of total
stations.
• Increase the number of total stations in the network
setting of the control station.
• Change the station number to the one that is within the
number of total stations.
E104
H
to
E10A
H
Parameter error
Some of the network
parameters is incorrect.
• Write correct network parameters to the programmable
controller.
• If the error persists even after taking the above action,
please consult your local Mitsubishi representative.
E10B
H
Parameter error
The CPU module or CC-Link
IE Controller Network module
does not support the added
function.
• Use a CPU module or CC-Link IE Controller Network
module that supports the added function.
Page 606, Appendix 3
• If the error persists even after taking the above action,
please consult your local Mitsubishi representative.
E10C
H
E10D
H
Network module error The hardware has failed. • Please consult your local Mitsubishi representative.
E110
H
to
E117
H
Parameter error
Some of the network
parameters is incorrect.
• Write correct network parameters to the programmable
controller.
• If the error persists even after taking the above action,
please consult your local Mitsubishi representative.
E11A
H
Start device No. error (LW)
The Basic model QCPU or
safety CPU's own send range
is set to LB/LW4000 or
higher.
• Check "LB/LW Setting(1)" in "Network Range
Assignment" of the control station.
E11B
H
Start device No. error (LB)
E11C
H
LB/LW setting (2) error (LW)
The Basic model QCPU or
safety CPU's own send range
is set in "LB/LW Setting(2)".
• Check "LB/LW Setting(2)" in "Network Range
Assignment" of the control station.
E11D
H
LB/LW setting (2) error (LB)
E11E
H
End device No. error (LW)
The Basic model QCPU or
safety CPU's own send range
is set to LB/LW4000 or
higher.
• Check "LB/LW Setting(1)" in "Network Range
Assignment" of the control station.
E11F
H
End device No. error (LB)
E120
H
UINI execution at control
station
The UINI instruction was
executed at a control station.
• Setting the station number with the UINI instruction is
not allowed for control stations.
Set it with a network parameter.
• Change the station type setting to Normal station, and
then retry it.
E121
H
Own station No. error (UINI
instruction)
With "Specify Station No. by
Parameter" selected in the
network parameters, the UINI
instruction was executed.
• Select "Specify Station No. by Program." in the network
parameters, and execute it again.