516
E122
H
Duplicated station No. (UINI
instruction)
Duplicated station No. was
set for the own station using
the UINI instruction.
• Change the own station No. setting in the control data,
and then retry the instruction.
• Change the other station's No. which is duplicated.
E123
H
Station No. already set (UINI
instruction)
After setting a station No. with
the UINI instruction, the
instruction was executed
again.
• Station No. setting with the UINI instruction is limited to
one time only.
Reset the CPU module, and then retry the instruction.
E130
H
Pairing setting error
Pairing is not set for the
station of a Redundant CPU.
• Check the pairing setting in "Network Range
Assignment" of the control station.
E131
H
Pairing setting error
Pairing is set for a station
other than Redundant CPUs.
E134
H
Network type mismatch
The network type set in the
control station differs from the
type set in the own station.
• Change the network type of the own station (normal
station) to the network type of the control station.
E135
H
Network type mismatch
The network type set in the
control station differs from the
type set in the own station.
• Change the network type of the own station (normal
station) to the network type of the control station.
E136
H
CPU that does not have the
send points extension
function is installed
The CC-Link IE extended
mode is set for the network
type in the CPU module that
does not have the send
points extension function.
• Replace with the CPU module that has the send points
extension function.
• Change the network type to the CC-Link IE mode.
E152
H
Link startup condition error
Link startup was attempted
from a station different from
the one where cyclic
transmission has stopped.
• Execute link startup from the station where cyclic
transmission has stopped.
• Execute the forced link startup.
E160
H
Invalid link startup/stop
direction
The link stop/startup direction
content (SW0000) was not
set properly.
• Check the setting and stop or restart cyclic
transmission.
E162
H
Link startup/stop reexecution
error (instructed by other
station)
Reexecution was attempted
during processing for cyclic
transmission stop/restart.
• Reexecute it after completing the processing for cyclic
transmission stop/restart.
E163
H
Link startup/stop reexecution
error (instructed by own
station)
E164
H
Link startup/stop reexecution
error (instructed by entire
system)
E165
H
Link startup/stop station
specification error
The link stop/startup direction
contents (SW0001 to
SW0008) were not set
properly.
• Check the setting and stop or restart cyclic
transmission.
E166
H
Link startup/stop group
specification error
The link stop/startup group
specification (SW0012 to
SW0013) is not correct.
E170
H
to
E172
H
Network module error The hardware has failed. • Please consult your local Mitsubishi representative.
E173
H
Communication test retry
error
During execution of the
communication test, the test
was retried.
• Reexecute it after completing the currently executing
communication test.
Error code Error Error detail Corrective action