9.5 JP/GP.WRITE (Data Write to Programmable Controllers on Other Stations)
9.5 JP/GP.WRITE (Data Write to Programmable Controllers
on Other Stations)
The WRITE instruction writes data to devices of a programmable controller on another station. (In units of words)
*1 T, C, D, W, ST, SD or SW can be used.
For SD/SW, data can be written within the setting range allowed for the user.
For details on SD/SW, refer to the following.
Manual for the CPU module and network module on the target station
• Instruction format
• Instruction format (Available when the own station has a Universal model QCPU)
*2 If the device setting in the PLC parameter is different between the own and target stations, use "(D1)" (with double
quotation marks) to specify.
(1) Setting data
Setting
data
Available devices
Internal device
(System, User)
File
register
R, ZR
Link direct device
J\
Intelligent
function
module device
U\G
Index
register Zn
Constant
Others
Bit Word Bit Word K,H $
(S1) — —
(S2) — —
(D1) —
*1
—
(D2) —
Setting data
*1
Description Data type
Jn
Network No. of the own station (1 to 239, 254)
254: The network specified in Valid module during other station access
Binary 16 bits
Un
Start I/O number of the own station's CC-Link IE Controller Network module
(00 to FE
H
: The higher two digits of the 3-digit I/O number)
(S1)
Start device of the own station that stores control data
( Page 354, Section 9.5 (2))
Device name
(S2) The own station's start device where write data are stored.
(D1)
Target station's start device to which data are to be written.
(A contiguous area for the write data length is required.)
JP.WRITE
Start contact
[Instruction format][Execution condition][Instruction symbol]
GP.WRITE
Start contact
JP.WRITE
Jn (S1) (S2) (D1) (D2)
GP.WRITE
Un (S1) (S2) (D1) (D2)
*2
*2
[Instruction format][Execution
condition]
[Instruction
symbol]
JP.WRITE
Start contact
GP.WRITE
Start contact
JP.WRITE
Jn (S1) (S2) "(D1)" (D2)
GP.WRITE
Un (S1) (S2) "(D1)" (D2)