EasyManua.ls Logo

Mitsubishi Electric MELSEC-Q Series - Page 356

Mitsubishi Electric MELSEC-Q Series
674 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
354
(2) Control data
Device Item Setting data Setting range
Setting
side
*1
(S1)+0
Execution/Error
completion type
0000
H
0001
H
0080
H
0081
H
User
1) Execution type (bit 0)
0: No arrival confirmation
• When the target station is on the same network
Completed when data are sent from the own station.
• When the target station is on another network
Completed when data reach a relay station on the same network.
1: With arrival confirmation
Completed when data are written to the target station.
When "0: No arrival confirmation" is specified, even if writing to the
target station is terminated abnormally in the following cases, it is
normal completion on the own station.
• Communication itself was completed normally, although the data
sent were erroneous.
• Data could not be written to the target station because instructions
from multiple stations were sent to the same station. (An error
code (E006
H
or E205
H
) is detected on the target station.)
2) Error completion type (bit 7)
Specify the clock data setup status for error completion.
0: Clock data at the time of error completion is not set in the area
starting from (S1)+11.
1: Clock data at the time of error completion is set in the area
starting from (S1)+11.
b15
002) 1)
b7 b0to to
Completed
Target
station
Request
source
Completed
Relay
station
Target
station
Request
source
Completed
Completed
Relay
station
Target
station
Target
station
Request
source

Table of Contents

Other manuals for Mitsubishi Electric MELSEC-Q Series

Related product manuals