CHAPTER 9 DEDICATED INSTRUCTIONS
9
9.5 JP/GP.WRITE (Data Write to Programmable Controllers on Other Stations)
(S1)+1 Completion status
The instruction completion status is stored.
0: Normal
Other than 0: Error ( Page 511, Section 10.2)
—System
(S1)+2
Channel used by
own station
*2
Specify the channel used by the own station. ( Page 328,
Section 9.2.2 (1))
1 to 10
(1 to 8 when the
own station is a
safety CPU)
User
(S1)+3
Target station's
CPU type
Specify the CPU module on the station to be accessed.
0000
H
03D0
H
to 03D3
H
03E0
H
to 03E3
H
03FF
H
User
Setting value Description
0000
H
Control CPU (The access target is the same as
when "03FF
H
" is specified.)
03D0
H
Control system CPU (Redundant CPU only)
03D1
H
Standby system CPU (Redundant CPU only)
03D2
H
System A CPU (Redundant CPU only)
03D3
H
System B CPU (Redundant CPU only)
03E0
H
• Target station CPU (single CPU system)
• Multi-CPU No.1
• Control CPU (single CPU system)
• Multiple CPU system No.1
03E1
H
Multiple CPU system No.2
03E2
H
Multiple CPU system No.3
03E3
H
Multiple CPU system No.4
03FF
H
Control CPU
When the instruction is executed with control system CPU (03D0
H
)
or standby system CPU (03D1
H
) specified, if system switching
occurs at the target station, the instruction execution may fail. (Error
code: 4244
H
, 4248
H
)
If the instruction has failed with the above error, execute it again.
(S1)+4
Target station
network No.
Specify the network No. of the target station.
1 to 239: Network No.
254: Specify this when 254 has been set in Jn.
1 to 239
254
User
Device Item Setting data Setting range
Setting
side
*1