Appendix 4 Comparison Between CC-Link IE Controller Network and MELSECNET/H
Appendix 4.3 Link special relays (SB) and link special registers (SW)
Appendix 4.3 Link special relays (SB) and link special registers
(SW)
This section compares link special relays (SB) and link special registers (SW) between CC-Link IE Controller Network
and MELSECNET/H.
Some link special relays (SB) and link special registers (SW) have been changed for the CC-Link IE Controller
Network.
Verify the link special relays (SB) and link special registers (SW). ( Page 639, Appendix 4.5)
(1) Comparison of link special relay (SB)
Change the link special relay (SB) in a sequence program referring to the following chart.
In addition, the link special relay (SB) shown below is a list for a case when an assignment range is SB0000 to
SB01FF.
(a) Comparison with the MELSECNET/H module
: compatible, : partially changed, —: incompatible
MELSECNET/H CC-Link IE Controller Network
Compatibility
Precautions for
replacement
No. Name No. Name
SB0000 Link startup (host) SB0000 Link startup (own station)
None
SB0001 Link stop (host) SB0001 Link stop (own station)
SB0002 System link startup SB0002 System link startup
SB0003 System link stop SB0003 System link stop
SB0005 Clear retry count — — —
Delete the sequence
program for the
corresponding part.
SB0006
Clear communication error
count
SB0006
Clear communication error
count
(Content
changed)
The area for clear target is
different in the CC-Link IE
Controller Network module.
SB0007
Clear forward loop
transmission errors
SB0007
Clear IN-side transmission
error counter
SB0008
Clear reverse loop
transmission errors
SB0008
Clear OUT-side
transmission error counter
SB0009 Clear loop switching counter SB0009 Clear loop switching counter
SB000A
Clear transient transmission
error counter
SB000A
Clear transient transmission
error counter
SB000B
Transient transmission error
area setting
——
—
Delete the sequence
program for the
corresponding part.
SB0011
Data link operation
designation
——
SB000F Minor error clear — —
SB0014
Remote sub-master station
switching command
——
SB0018
System switching monitoring
time setting valid flag
——
SB0020 Module status SB0020 Module status
None
SB0040 Network type (host) SB0040 Network type (own station)
SB0041
Host station's redundant
function support information
SB0041
Host station's redundant
function support information
None
SB0042 Power supply status of host SB0042 Power supply status of host None