6.9 Routing Parameters
Set a relay station in the own network to transmit data to another network.
Set the routing parameters under one of the following conditions.
When using the dedicated instruction to perform transient transmission to a different network ( Page
324, CHAPTER 9)
When using the IP packet transfer function ( Page 106, Section 4.3)
For the routing function, refer to the following.
Page 103, Section 4.2.3
Up to 64 routing information settings are available for one programmable controller.
Setting the same target network No. is not allowed.
1. Open the "Setting the Ethernet/CC IE/MELSECNET Routing Information" window in the
programming tool.
Project window [Parameter] [Network Parameter] [Ethernet/CC IE/MELSECNET]
button
2. Configure settings with reference to the description below.
3. Click the button.
Item Description
Target Network No.
Set a network No. of another network.
(Setting range: 1 to 239, Default: None)
Relay Network No.
Set the own network No.
(Setting range: 1 to 239, Default: None)
Relay Station No.
Set the station No. of the relay station in the own network.
(Setting range for Universal model QCPU: 0 to 120, Default: None)
(Setting range for other than Universal model QCPU: 0 to 64, Default: None)