204
6.5 Refresh Parameters
6.5.1 Refresh parameter setting
Set the range of the transfer between the link devices of the CC-Link IE Controller Network module and CPU module
devices.
The number of refresh parameter settings per module is shown below.
*1 For the safety CPU with a serial number (first five digits) of "14051" or earlier, the number of refresh parameter settings
per module (except for SB/SW transfer) is 8.
LB/LW data can be transferred exceeding the B/W capacity of the CPU module (8K points). ( Page 212, Section
6.5.2)
The link device data of a CC-Link IE Controller Network module can be directly read/written by a sequence program.
( Page 70, Section 4.1.4)
1. Configure the network setting. ( Page 180, Section 6.2)
2. Open the setting window in the programming tool.
Project window [Parameter] [Network Parameter] [Ethernet/CC IE/MELSECNET]
button
3. Configure settings with reference to the description below.
4. Click the button.
Item
Number of settings
Basic model
QCPU
High Performance model QCPU,
Process CPU, Redundant CPU,
Q00UJCPU, Q00UCPU, Q01UCPU,
and safety CPU
*1
Universal model QCPU
(other than Q00UJCPU,
Q00UCPU, and Q01UCPU)
Link device transfer 8 64 256
SB/SW transfer 1 for each