248
(2) For Universal model QCPUs
Universal model QCPUs transfer interlink data in several batches.
(a) Interlink transmission time taken in one END processing
*1 The number of words that can be transferred in one END (N) is restricted as follows:
N = Sequence scan time (under no interlink transmission parameter setting) (µs) × 0.05
*1 Indicates base units on which the network module of the transfer source is mounted.
*2 Indicates base units on which the network module of the transfer destination is mounted.
L: Interlink transmission time taken in one END processing
n1: Number of lines where interlink transmission parameters are set
LBr: Total number of LB points, which are set with interlink transmission parameters
LWr: Total number of LW points, which are set with interlink transmission parameters
KM4, KM5, and KM6: Constants
CPU type
KM4(×10
-3
) KM5(×10
-3
)
Universal
model
QCPU
Q00UJ/Q00U/Q01UCPU
Q02UCPU 120 11
Q03UD/Q03UDECPU 34 16.3
Q04UDH/Q04UDEH/Q06UDH/Q06UDEH/
Q10UDH/Q10UDEH/Q13UDH/Q13UDEH/
Q20UDH/Q20UDEH/Q26UDH/Q26UDEH/
Q50UDEH/Q100UDEHCPU
25 16.3
Q03UDV/Q04UDV/Q06UDV/Q13UDV/
Q26UDVCPU
12 4
CPU type
KM6(×10
-3
)
Main base
*1
Main base
*2
Main base
*1
Extension
base
*2
Extension
base
*1
Main base
*2
Extension
base
*1
Extension
base
*2
Universal
model
QCPU
Q00UJ/Q00U/Q01UCPU
Q02UCPU 0.76 1.27 1.37 1.79
Q03UD/Q03UDECPU 0.73 1.27 1.37 1.78
Q04UDH/Q04UDEH/Q06UDH/Q06UDEH/
Q10UDH/Q10UDEH/Q13UDH/Q13UDEH/
Q20UDH/Q20UDEH/Q26UDH/Q26UDEH/
Q50UDEH/Q100UDEHCPU
0.73 1.25 1.35 1.78
Q03UDV/Q04UDV/Q06UDV/Q13UDV/
Q26UDVCPU
0.73 1.27 1.37 1.78
L KM4 (KM5 n1) KM6 [ms]