CHAPTER 4 FUNCTIONS
4
4.3 IP Packet Transfer Function
4.3.5 Precautions
(6) Precautions when configuring a multiple CPU system
Set a CPU module connected to an Ethernet device as a control CPU of the CC-Link IE Controller Network
module performing the IP packet transfer.
Any relay station on CC-Link IE Controller Network can be served as a control CPU of the CC-Link IE Controller
Network module transferring the IP packet.
When multiple CC-Link IE Controller Network modules with the same network number are connected to one
system, the CC-Link IE Controller Network module with the smallest slot number transfers the IP packet.
To transfer the IP packet, connect the Ethernet device to a control CPU of the CC-Link IE Controller Network
module with the same network number and the smallest slot number.
1
2
3
Ethernet
Ethernet
Ethernet device
(request source device)
CC-Link IE Controller Network
Control
Ethernet device
(request destination device)
CPU module connected to
an Ethernet device
CPU module on
CC-Link IE Controller Network
(No restrictions on the control CPU)
3
Ethernet
Ethernet device
(request source device)
CC-Link IE Controller
Network
Control
Module mounted on
the smallest slot No.
Same network No.