5.7 Test Before CC-Link IE Controller Network Operation
5.7.1 Communication test
(d) Routing parameters of the relay station 1
(e) Routing parameters of the relay station 2
(3) Executing the communication test
1. Open the "Communication Test" window in the programming tool.
[Diagnostics] [CC IE Control Diagnostics] button
2. Configure settings with reference to the description below.
3. Click the button.
Item Description
Target Station
Network No.
Set the network No. of the communication target.
(Setting range: 1 to 239, Default: 1)
Station No.
Set the station No. of the communication target.
(Setting range for Universal model QCPU: 0 to 120, Default: 1)
(Setting range for other than Universal model QCPU: 0 to 64, Default: 1)
Communication
Data Setting
Data Length
Set the length of the communication data.
(Unit: Bytes) (Setting range: 1 to 900, Default: 100)
Communication Count
Set the number of communications.
(Setting range: 1 to 100, Default: 1)
Communication Timeout
Set a timeout time of the communication test. (Unit: Seconds)
(Setting range: 1 to 100, Default: 5)