CHAPTER 6 PARAMETER SETTING
6
6.6 Interrupt Settings
(1) Intelligent function module interrupt pointer setting
Interrupt (SI) Nos. of the CC-Link IE Controller Network module set in "Interrupt Settings" are linked to interrupt
pointers of the CPU module.
1. Open the "Intelligent Function Module Interrupt Pointer Setting" window of the programming tool.
Project window [PLC Parameter] [PLC System] button
2. Configure settings with reference to the description below.
3. Click the button.
Item Description
PLC Side
Interrupt Pointer Start No.
Set the Start No. of the interrupt program (I ).
(Setting range: 50 to 255, Default: None)
Interrupt Pointer Count
Set the number of interrupt conditions.
(Setting range: 1 to 16, Default: None)
Intelligent Module
Side
Start I/O No.
Set a start I/O No. of the CC-Link IE Controller Network module.
(Setting range: 0000
H
to 0FE0
H
, Default: None)
Start SI No.
Set a start interrupt (SI) No. of the CC-Link IE Controller Network
module.
(Setting range: 0 to 15, Default: None)