CHAPTER 6 PARAMETER SETTING
6
6.8 Interlink Transmission Parameters
(c) Interlink transmission is performed between the control station and normal station.
(The MELSECNET/H standby station cannot be the target of the interlink transmission.)
(d) The transfer source link device data can be transferred to multiple network modules.
(An identical transfer source link device can be specified.)
(2) Interlink transmission parameter setting example
The interlink transmission parameters for the following assignment are shown in this section.
• Interlink transmission parameter setting for Module 1  Module 2
CPU module
1M
P1
1N
S2
1N
S3
1N
S3
2M
P1
2M
P1
2N
S2
2N
S3
0
3FF
13FF
1FFF
1000
LB LB
B
1000 to 101F
1020 to 103F
100 to 11F
200 to 21F
1300 to 131F
0 to 1F
1M
P11NS22NS22NS3
Network No.1
Network No.2
Link refresh
range
The transfer target link
devices do not turn
ON/OFF since they are
not set within the link
refresh range.
B1000
B1300
B0
B200
B1300
B200 B1000
B0
B280