254
(a) System configuration and conditions
(b) Link scan time ( Page 244, Section 7.1)
Item Description
CPU module Q06UDHCPU
Total number of stations per network 3 stations
Total link device points
LB/LW 1024 points for each
LX/LY 0 point
SB/SW 512 points for each
Sequence scan time 1ms
File register None
Interlink transmission
1N
S
3 ï‚® 2M
P
1(LB
T
)
64 points
1N
S
3  2M
P
1(LB
T
)
32 points
Transient transmission None
CC-Link IE Controller Network module Installed to slot 0 of main base unit
Faulty station None
LS = [KB + (N × 56) + {LB + LY + (LW × 16)}  8 × 0.016 + (N
T
× T × 30)]  1000 + Nc [ms]
(1) Sending-side link refresh time, receiving-side link refresh time
LS
T
, LS
R
= [1100 + (3 × 56) + {1024 + 0 + (1024 × 16)}  8 × 0.016 + (0 × 2 × 30)]  1000
= 1.30 [ms]