322
(d) RRUN/RSTOP/RTMRD/RTMWR instruction
1. Create an interlock with the following link special relay (SB) and link special register (SW) before
executing an instruction.
• Baton pass status (own station) (SB0047)
• Baton pass status of each station (SB00A0) (When all stations are specified)
• Baton pass status of each station (SB00A0 to SW00A7)
2. If the instruction failed, an error code is stored in Send/receive instruction processing result
(SW0030 to SW0037) corresponding to the channel used by the own station.
Check the error and take corrective actions according to the error code. ( Page 511, Section 10.2)
(e) RIRD/RIWT instruction
Create an interlock with the following link special relay (SB) and link special register (SW) before executing an
instruction.
• Baton pass status (own station) (SB0047)
• Baton pass status of each station (SB00A0 to SW00A7)
No. Description No. Description
SB0047 Baton pass status (own station) —
—
SW0030 Send/receive instruction (1) processing result
SW0031 Send/receive instruction (2) processing result
SW0032 Send/receive instruction (3) processing result
SW0033 Send/receive instruction (4) processing result
SW0034 Send/receive instruction (5) processing result
SW0035 Send/receive instruction (6) processing result
SW0036 Send/receive instruction (7) processing result
SW0037 Send/receive instruction (8) processing result
SB00A0 Baton pass status of each station
SW00A0
to
SW00A7
Baton pass status of each station
No. Description No. Description
SB0047 Baton pass status (own station) —
—
SW00A0
to
SW00A7
Baton pass status of each station