401
CHAPTER 9 DEDICATED INSTRUCTIONS
9
9.9 JP/GP.SEND (Data Transmission to Programmable Controllers on Other Stations)
(2) Control data
Device Item Setting data Setting range
Setting
side
*1
(S1)+0
Execution/Error
completion type
0000
H
0001
H
0080
H
0081
H
User
1) Execution type (bit 0)
0: No arrival confirmation
• When the target station is on the same network
Completed when data are sent from the own station.
• When the target station is on another network
Completed when data reach a relay station on the same network.
1: With arrival confirmation
Completed when data are stored in the specified channel area of
the target station.
When "0: No arrival confirmation" is specified, even if transmission to
the target station is terminated abnormally in the following cases, it is
normal completion on the own station.
• Communication itself was completed normally, although the data
sent were erroneous.
• Data could not be stored in the target station because instructions
from multiple stations were sent to the same station. (An error
code (E006
H
or E205
H
) is detected on the target station.)
2) Error completion type (bit 7)
Specify the clock data setup status for error completion.
0: Clock data at the time of error completion is not set in the
area starting from (S1)+11.
1: Clock data at the time of error completion is set in the area
starting from (S1)+11.
b15
002) 1)
b7 b0to to
Completed
Target
station
Request
source
Completed
Relay
station
Target
station
Request
source
Completed
Completed
Relay
station
Target
station
Target
station
Request
source