403
CHAPTER 9 DEDICATED INSTRUCTIONS
9
9.9 JP/GP.SEND (Data Transmission to Programmable Controllers on Other Stations)
*1 The setting side is as shown below.
User: Before execution of the link dedicated instruction, data must be set by the user.
System: The CPU module stores the execution result of the link dedicated instruction.
*2 Data is not stored when Completion status ((S1)+1) is "Channel busy (Dedicated instruction) (error code: E26C
H
)".
*3 Logical channel setting is not available for the CC-Link IE Controller Network module. ( Page 615, Appendix 4.2
(1))
(S1)+9 Send data length
Specify the send data size of (S2) to (S2)+n.
When the target station is QCPU/RCPU/LCPU: 1 to 960 words
When the target station is QnACPU: 1 to 480 words
When the target station has a QCPU, check the version of the
network module on the target station.
The size of receive data is restricted depending on the version.
( Manual for the network module on the target station)
1 to 960 User
(S1)+10 — Unused 0 User
(S1)+11
Clock set flag
The valid or invalid status of the data in the area starting from
(S1)+12 is stored. Data is stored only when 1 is set in the bit 7 of
Execution/Error completion type ((S1)+0). Note that the stored value
will not be cleared even after the dedicated instruction is completed.
0: Invalid
1: Valid
—System
(S1)+12
to
(S1)+15
Clock data on
error completion
Clock data on error completion are stored in BCD format. Data is
stored only when 1 is set in the bit 7 of Execution/Error completion
type ((S1)+0). Note that the stored value will not be cleared even
after the dedicated instruction is completed.
When the target station is QnACPU, "00
H
" is stored in the Year field
(first two digits of the year).
—System
(S1)+16
Error-detected
network No.
*2
Network No. of the station, where an error was detected, is stored.
Data is stored only when 1 is set in the bit 7 of Execution/Error
completion type ((S1)+0). Note that the stored value will not be
cleared even after the dedicated instruction is completed.
1 to 239: Network No.
—System
(S1)+17
Error-detected
station No.
*2
Station No. of the station, where an error was detected, is stored.
Data is stored only when 1 is set in the bit 7 of Execution/Error
completion type ((S1)+0). Note that the stored value will not be
cleared even after the dedicated instruction is completed.
1 to 120: Station No.
—System
Device Item Setting data Setting range
Setting
side
*1
(S1)+12
(S1)+13
(S1)+14
(S1)+15
Month (01
H to 12H)
Hour (00
H to 23H)
Second (00
H to 59H)
Day (01
H to 31H)
Minute (00
H to 59H)
00
H (Sun.) to 06H (Sat.)
Day of week (00
H to 06H)
Year (00
H
to 99
H
), First 2 digits
Year (00
H
to 99
H
), Last 2 digits
b15 b8 b7to b0to