414
(2) Control data
Device Item Setting data Setting range
Setting
side
*1
(S1)+0
Error completion
type
1) Error completion type (bit 7)
Specify the clock data setup status for error completion.
0: Clock data at the time of error completion is not set in the
area starting from (S1)+11.
1: Clock data at the time of error completion is set in the area
starting from (S1)+11.
0000
H
0080
H
User
(S1)+1 Completion status
The instruction completion status is stored.
0: Normal
Other than 0: Error ( Page 511, Section 10.2)
— System
(S1)+2
Own station
channel
Specify the channel of the own station, where receive data are
stored.
( Page 328, Section 9.2.2 (1))
1 to 8 User
(S1)+3
Channel used by
sending station
Stores the channel used by the sending station. — System
(S1)+4
Network No. of
sending station
Stores network No. of the sending station.
1 to 239: Network No.
— System
(S1)+5
Sending station
No.
Stores station No. of the sending station.
1 to 120: Station No.
— System
(S1)+6 — Unused 0User
(S1)+7 — Unused 0User
(S1)+8
Arrival monitoring
time
Specify the monitoring time required for instruction completion.
If not completed within the time, the instruction is terminated with an
error.
0: 10 seconds
1 to 32767: 1 to 32767 seconds
0 to 32767 User
(S1)+9
Receive data
length
Stores the receive data size stored in (D1) to (D1)+n.
1 to 960: Receive data size (words)
— System
(S1)+10 — Unused 0User
(S1)+11
Clock set flag
The valid or invalid status of the data in the area starting from
(S1)+12 is stored. Data is stored only when 1 is set in the bit 7 of
Error completion type ((S1)+0). Note that the stored value will not be
cleared even after the dedicated instruction is completed.
0: Invalid
1: Valid
— System
(S1)+12
to
(S1)+15
Clock data on
error completion
Clock data on error completion are stored in BCD format. Data is
stored only when 1 is set in the bit 7 of Error completion type
((S1)+0). Note that the stored value will not be cleared even after the
dedicated instruction is completed.
— System
b15
001)
b7 to b0to
(S1)+12
(S1)+13
(S1)+14
(S1)+15
Month (01
H to 12H)
Hour (00
H to 23H)
Second (00
H to 59H)
Day (01
H to 31H)
Minute (00
H to 59H)
00
H (Sun.) to 06H (Sat.)
Day of week (00
H to 06H)
Year (00
H
to 99
H
), First 2 digits
Year (00
H
to 99
H
), Last 2 digits
b15 b8 b7to b0to