444
(1) Setting data
Setting data
*1
Description Data type
"Jn"/Jn
Network No. of the target station (1 to 239, 254)
254: The network specified in Valid module during other station access
String/
Binary 16 bits
"Un"/Un
Start I/O number of the own station's CC-Link IE Controller Network module
(00 to FE
H
: The higher two digits of the 3-digit I/O number)
n1
Channel used by own station (1 to 8)
Specify the channel used by the own station. ( Page 328, Section 9.2.2
(1))
Specify the channel used by own station that is the same as the one used for
the RSTOP instruction.
Binary 16 bits
n2
Target station No.
Specify the station No. of the target station.
(1) Station No. specification
When own station is Universal model QCPU: 1 to 120
When own station is other than Universal model QCPUs: 1 to 64
(2) Group specification
81
H
to A0
H
: All stations of a group (No.1 to 32)
(3) All stations
FF
H
: All stations of the target network No. (Except the own station)
To specify a group or all stations
• Set "0000
H
" or "03FF
H
" for Target station's CPU type (n3). ( Page 329,
Section 9.2.2 (3))
• When the target station is on the CC-Link IE Field Network, stations cannot
be specified as a group.
• To check if data has been properly written in the target station, check if the
CPU module on the target station of the write destination is in the RUN
status.
n3
Specify the CPU module on the station to be accessed.
Set value Description
0000
H
Control CPU (The access target is the same as when
"03FF
H
" is specified.)
03D0
H
Control system CPU (Redundant CPU only)
03D1
H
Standby system CPU (Redundant CPU only)
03D2
H
System A CPU (Redundant CPU only)
03D3
H
System B CPU (Redundant CPU only)
03E0
H
• Target station CPU (single CPU system)
• Multi-CPU No.1
• Control CPU (single CPU system)
• Multiple CPU system No.1
03E1
H
Multiple CPU system No.2
03E2
H
Multiple CPU system No.3
03E3
H
Multiple CPU system No.4
03FF
H
Control CPU
When the instruction is executed with control system CPU (03D0
H
) or standby
system CPU (03D1
H
) specified, if system switching occurs at the target station,
the instruction execution may fail. (Error code: 4244
H
, 4248
H
)
If the instruction has failed with the above error, execute it again.