CHAPTER 9 DEDICATED INSTRUCTIONS
9
9.14 Z(P).RRUN (Remote RUN)
(4) Program example
The following shows a program in which a remote RUN request is sent to the QCPU of station No.2 (target
station) when M171 turns ON.
(a) System configuration example
(b) Devices used in the program example
• Special relay (SM), link special relay (SB), and link special register (SW)
Remark
• For details of link special relay (SB): Page 568, Appendix 1
• For details of link special register (SW): Page 584, Appendix 2
• Devices used by the user
Device Description Device Description
SM400 Always ON SW0032 Send/receive instruction (3) processing result
SB0047 Baton pass status (own station) SW00A0.1 Baton pass status of station No.2
Device Description Device Description
M171 Start contact M176 Completion status indication device
M175 Completion device D618 Error code storage device
CPU module
RRUN RUN
RRUN
instruction
request
source
(Own station)
RRUN
instruction
request
target
(Target station)
CC-Link IE
Controller
Network module
Channel 3
CPU module CC-Link IE
Controller
Network module
CPU module CC-Link IE
Controller
Network module
CPU module CC-Link IE
Controller
Network module
Network No.1
Station No.1 Station No.2
Station No.4 Station No.3