453
CHAPTER 9 DEDICATED INSTRUCTIONS
9
9.15 Z(P).RSTOP (Remote STOP)
*1 Local devices and file registers for each program cannot be used as devices in setting data.
Remote STOP is available when the RUN/STOP switch of the target station CPU is set to "RUN".
Remote STOP is not executable when system protect is applied to the target station CPU.
If the target station CPU, for which remote STOP was performed, is reset, the remote STOP information is erased.
(2) Function
(a) RSTOP instruction overview
The RSTOP instruction executes remote STOP to the target station CPU.
The target station is specified in Target station network No. (Jn) and Target station No. (n2).
Upon completion of the request to the target station, the completion device (D1) turns ON.
(b) Target stations available for specification
Target network
In addition to CC-Link IE Controller Network, stations in the following networks can be also specified.
CC-Link IE Field Network
MELSECNET/H
MELSECNET/10
Ethernet
Target station's CPU type
The RSTOP instruction is executable only when the target station is QCPU, RCPU, or LCPU.
n4
Operation mode
Binary 16 bits
(D1)
The own station's device that is turned on for one scan upon completion of the
instruction
(D1)+1 also turns ON if the instruction execution has failed.
Bit
Setting data
*1
Description Data type
b15
0001
H (Fixed)
b0to
STOP
CC-Link IE Controller
Network module
CPU module CPU module
RSTOP
Network module
n4
Channel 1
Channel n
Channel 8
[Own station] [Target station]